222 Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A Parameter Information
246 MVA Un A Lvl MVA 0/1000 0.00 Allows the user to enter a value for the MVA Under Alarm Level
(MVA Un A Lvl). If the current actual value of the Apparent
Power (MVA) is less than the MVA Un A Lvl for a time period
greater than that defined by MVA Un A Dly, a MVA Un Alarm will
be signaled.
R/W
247 MVA Un A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Apparent Power
Under Alarm Delay (MVA Un A Dly). If the current actual value of
the Apparent Power (MVA) is less than the MVA Un A Lvl for a
time period greater than that defined by MVA Un A Dly, a MVA
Un Alarm will be signaled.
R/W
248 Lead PF Ov F Lvl 0/1 0.00 Allows the user to enter a value for the Leading Power Factor
Over Fault Level (Lead PF Ov F Lvl). If the current actual Power
Factor value is leading more than the Lead PF Ov F Lvl for a time
period greater than that defined by Lead PF Ov F Dly, a Lead PD
Ov Fault will be signaled.
R/W
249 Lead PF Ov F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Leading Power
Factor Over Fault Delay (Lead PF Ov F Dly). If the current actual
Power Factor value is leading more than the Lead PF Ov F Lvl for
a period greater than that defined by Lead PF Ov F Dly, a Lead
PD Ov fault will be signaled.
R/W
250 Lead PF Ov A Lvl 0/1 0.00 Allows the user to enter a value for the Leading Power Factor
Over Alarm Level (Lead PF Ov A Lvl). If the current actual Power
Factor value is leading more than the Lead PF Ov A Lvl for a
period greater than that defined by Lead PF Ov A Dly, a Lead PD
Ov alarm will be signaled.
R/W
251 Lead PF Ov A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Leading Power
Factor Over Alarm Delay (Lead PF Ov A Dly). If the current actual
Power Factor value is leading more than the Lead PF Ov A Lvl for
a period greater than that defined by Lead PF Ov A Dly, a Lead
PD Ov alarm will be signaled.
R/W
252 Lead PF Un F Lvl 0/1 0.00 Allows the user to enter a value for the Leading Power Factor
Under Fault Level (Lead PF Un F Lvl). If the current actual Power
Factor value is leading less than the Lead PF Un A Lvl for a time
period greater than that defined by Lead PF Un A Dly, a Lead PD
Un Fault will be signaled.
R/W
253 Lead PF Un F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Leading Power
Factor Under Fault Delay (Lead PF Un F Dly). If the current actual
Power Factor value is leading less than the Lead PF Un A Lvl for a
time period greater than that defined by Lead PF Un A Dly, a
Lead PD Un Fault will be signaled.
R/W
254 Lead PF Un A Lvl 0/1 0.00 Allows the user to enter a value for the Leading Power Factor
Under Alarm Level (Lead PF Un A Lvl). If the current actual
Power Factor value is leading less than the Lead PF Un A Lvl for a
time period greater than that defined by Lead PF Un A Dly, a
Lead PD Un Alarm will be signaled.
R/W
255 Lead PF Un A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Leading Power
Factor Under Alarm Delay (Lead PF Un A Dly). If the current
actual Power Factor value is leading less than the Lead PF Un A
Lvl for a time period greater than that defined by Lead PF Un A
Dly, a Lead PD Un Alarm will be signaled.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number Name Unit Min/Max Default Enum Text Description R/W