Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019 223
Parameter Information Appendix A
256 Lag PF Ov F Lvl -1/0 0.00 Allows the user to enter a value for the Lagging Power Factor
Over Fault Level (Lag PF Ov F Lvl). If the current actual Power
Factor value lags more than the Lag PF Ov F Lvl for a time period
greater than that defined by Lag PF Ov F Dly, a Lag PF Ov Fault
will be signaled.
R/W
257 Lag PF Ov F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Lagging Power
Factor Over Fault Delay (Lag PF Ov F Dly). If the current actual
Power Factor value lags more than the Lag PF Ov F Lvl for a time
period greater than that defined by Lag PF Ov F Dly, a Lag PF Ov
Fault will be signaled.
R/W
258 Lag PF Ov A Lvl -1/0 0.00 Allows the user to enter a value for the Lagging Power Factor
Over Alarm Level (Lag PF Ov A Lvl). If the current actual Power
Factor value lags more than the Lag PF Ov A Lvl for a time period
greater than that defined by Lag PF Ov A Dly, a Lag PF Ov Alarm
will be signaled.
R/W
259 Lag PF Ov A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Lagging Power
Factor Over Alarm Delay (Lag PF Ov A Dly). If the current actual
Power Factor value lags more than the Lag PF Ov A Lvl for a time
period greater than that defined by Lag PF Ov A Dly, a Lag PF Ov
Alarm will be signaled.
R/W
260 Lag PF Un F Lvl -1/0 0.00 Allows the user to enter a value for the Lagging Power Factor
Under Fault Level (Lag PF Un F Lvl). If the current actual Power
Factor value lags less than the Lag PF Un F Lvl for a time period
greater than that defined by Lag PF Un F Dly, a Lag PF Un Fault
will be signaled.
R/W
261 Lag PF Un F Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Lagging Power
Factor Under Fault Delay (Lag PF Un F Dly). If the current actual
Power Factor value lags less than the Lag PF Un F Lvl for a time
period greater than that defined by Lag PF Un F Dly, a Lag PF Un
Fault will be signaled.
R/W
262 Lag PF Un A Lvl -1/0 0.00 Allows the user to enter a value for the Lagging Power Factor
Under Alarm Level (Lag PF Un A Lvl). If the current actual Power
Factor value lags less than the Lag PF Un A Lvl for a time period
greater than that defined by Lag PF Un A Dly, a Lag PF Un Alarm
will be signaled.
R/W
263 Lag PF Un A Dly Secs 0.1/99 0.1 Allows the user to enter a time value for the Lagging Power
Factor Under Alarm Delay (Lag PF Un A Dly). If the current
actual Power Factor value lags less than the Lag PF Un A Lvl for a
period greater than that defined by Lag PF Un A Dly, a Lag PF Un
alarm will be signalled.
R/W
264 Motor Restart En
(Refer to 264)
Manual P111:
The SMC-50 can be configured to automatically reset the
overload fault when it has cooled to the set Overload Reset
Level, Parameter 80. The Motor Restart Enabled (Motor Restart
En), Parameter 264, must be enabled (Overload = Set) to allow
the Overload Reset Level parameter to function.
Table 66 - SMC -50 Parameter List (Continued)