278 Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix G Using DeviceLogix
• Activate the Critical High Level Pilot when the Critical High Level
sensor is active.
• Reset alarms / faults with a Reset push button input
Parameter Configuration
The parameters that are listen in Table 8 0 are configured for this example.
Table 80 - Wet Well Parameter Configuration
Port Parameter No. Parameter Value Description
0.148.14
Host Parameter #148
Bit #14
“Logic Mask” Set bit #14 Allow DeviceLogix to control the motor.
8.6
Port #8
Parameter #6
“Aux 1 Config” “Device Logix ”
Auxiliary #1 is used to control the Sensor Failure
pilot light. In order for DeviceLogix to control the
Auxiliary it must be configured to “Device Logix”.
8.10
Port #8
Parameter #10
“Aux 2 Config” “Device Logix”
Auxiliary #2 is used to control the Critical Level
pilot light. In order for DeviceLogix to control the
Auxiliary it must be configured to “Device Logix”.