• Menu: ConfigurationÆSystemÆViewÆVerbose • Menu: ConfigurationÆSystemÆViewÆVerbose
Enables the user to scroll through detected frames, and through the slots within the frame. Each entry
displays the frame number and software version; and one slot configuration comprising the amplifier
software version, amplifier type, and surveillance mode.
Enables the user to scroll through detected frames, and through the slots within the frame. Each entry
displays the frame number and software version; and one slot configuration comprising the amplifier
software version, amplifier type, and surveillance mode.
Where:
‘Single’: Identifies a single circuit surveillance mode.
‘Dual’: Identifies a dual circuit surveillance mode.
‘Loop’: Identifies a loop return surveillance mode.
‘Standby’: Identifies a standby amplifier.
25.6.2 Amplifier Changeover Testing
It is possible to test changeover to a standby amplifier and change back provided that the selected amplifier
is connected to an available standby amplifier (and is not a standby amplifier itself).
• Changeover to Standby Amplifier:
Menu: TestÆChangeover
• Change back:
Menu: TestÆChange Back
• Once changed over, Change Back must be selected manually.
• Take care not to leave an amplifier in a changed over state.
• Pressing FAULT CLEAR undoes all active changeovers.
!
!