VAR8 and Variants Operation, Commissioning, Fault Finding, and Maintenance Guide
sue: 02 complete, approved
-
Is
Page 63 of 166 Page 63 of 166
To Modify the Emergency Class of a DVA Input: To Modify the Emergency Class of a DVA Input:
3. Select the DVA input, and then modify its emergency class as required. 3. Select the DVA input, and then modify its emergency class as required.
Menu: ConfigurationÆSystemÆRouterÆInputsÆDVAÆDVA #<n>ÆClass Menu: ConfigurationÆSystemÆRouterÆInputsÆDVAÆDVA #<n>ÆClass
On networked units, for correct indication of the emergency DVA message status on the
ACU’s front panel, as described in Table 6, the EVACUTE DVA should be set to ‘High
Priority Emergency’, the ALERT DVA should be set to ‘Low Priority Emergency’, and the
remaining audio sources should be set to ‘Non Emergency’ as specified in the system
default settings.
The system default setting is:
DVA Input 1 (DVA1) - EVACUATE: High Priority Emergency
DVA Input 2 (DVA2) - ALERT: Low Priority Emergency
DVA Inputs 3 and 4 (DVA3 and DVA4): Non Emergency
Mic/Line Inputs: Non Emergency
Music Input: Non Emergency
Mute Input: Non Emergency
Changes to the system default settings may result in an inappropriate indication of the
status of the zone group.
!
!