A 25
700 -00 Protocol name of the DLX
Table value: S C T M - D L X
Expl.: The protocol name of the DLX is SCTM-DLX
700 -01 Version of the DLX
Table value: V e r . x . y y . z z
Example: V e r . 1 . 0 0 . 0 0
Expl.: The version of the DLX is Ver. 1.00.00
700 -02 Version date
Table value: M M M D D Y Y Y Y
MMM: Month
DD: Day
YYYY: Year
Example: J a n 9 1 9 9 8
Expl.: The version date of the DLX is the 9th of January 1998
700 -03 Manufacturer name
Table value: B a e R G m b H
700 -2y Device status of the registration period (from version 1.03.08 and up)
y: desired registration period
1 MP1
2 MP2
Table value:
S15
S14
S13
S12
S11
S10
S9 S8 S7 S6 S5 S4 S3 S2 S1 S0
S0: Restart
S1: Parameter change
S2: Manual change of register (counter) values
S3: Power failure
S4: Warning
S5: Fault
S6: Manual Change of time or corrected by radio clock by more than 1
minute
S7: Test mode
S8: Change of state of a logic input
S9: Summer/Wintertime switching
Example:
0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1
Expl.: In this registration period a power failure of more than 200 ms has oc-
curred. The bits S0 (Restart), S3 (Power failure) and S4 (Warning) are
marked (set).
700 -80 Required memory capacity for SRAM cards
Table value: S S S S S S S S S S S S
Example: 2 5 4 2 0 8
Expl.: When a SRAM card is used, 254208 byte will be written to the card:
the card must have a minimum capacity of 256 kByte.
700 -81 Required memory capacity for FLASH cards
Table value: S S S S S S S S S S S S
Example: 1 1 7 9 6 4 8
Expl.: When a FLASH card is used, 1179648 byte will be written to the card:
the card must have a minimum capacity of 2 MByte.