A 30
901 -02 Reset blockage in number of registration periods MP1
Table value: R
R R
RRR: Reset blockage in number of registration periods MP1
Example: 0 0 3
Expl.: At least 3 registration periods MP1 need to pass between two resets
901 -03 Automatic Reset (yes/no)
Table value: A
A: Flag
0: automatic resets are disabled
1: automatic resets are enabled
Example: 0
Expl.: Automatic reset is disabled. Resets are initiated via the keypad on the front
panel or via the RST input.
901 -04 Frequency of automatic resets
Table value: F
F: Frequency
0: daily
1: weekly
2: monthly
3: annually
Example: 2
Expl.: One reset per month will be initiated automatically.
901 -05 Date and time of automatic resets
Table value: M
M D D h h m m
MM: Month (unused for daily, weekly and monthly resets)
DD: Day (unused for daily resets; for weekly resets: weekday; for
monthly resets: day of the month)
hh mm: hour minute
Example: 0 1 0 0 0 0
Expl.: The reset will take place on the first day of each month at 00:00.