INTRODUCTION
SPECIFICATIONS
1 - 6 I-E96-506B1
®
IEPAS02 and IEPAF02 power
module characteristics:
(continued)
Output current/voltage/
regulation/power:
(Line regulation is less than
0.5% on all outputs.
All tolerances are maximum tol-
erances and cumulative.)
Minimum output hold up time 17 msecs, output fully loaded
Heat dissipation 30 W per module maximum
Mounting Power supply modules mount in a single slot of the module mounting unit
or power mounting unit.
IEPEP01/02/03
characteristics:
AC input monitoring and transfer
low voltage detect
96 VRMS (
±
6 VRMS) for 120 VAC nominal input
192 VRMS (
±
12 VRMS) for 240 VAC nominal input
Line interrupt detect time 2.3 msecs to 3.2 msecs
Redundant AC transfer time 16 msecs maximum (IEPEP03 only)
Maximum current 20 A
IEPEP03 characteristics:
Monitor trip points
Status and alarm requirements:
Power system alarm output to
system common
Open to alarm, 24 VDC maximum, 120 mA (inductive loads require diode
suppression)
Bus voltage alarm output Open to alarm, 24 VDC maximum, 120 mA (inductive loads require diode
suppression)
Status signal inputs Normally open (NO) or normally closed (NC) jumper selectable on BMM
module. Low
≤
0.8 VDC, High
≥
3.1 VDC at bus monitor test points
IEFAN01/02 power
requirements
Table 1-4. Specifications
(continued)
Property Characteristics
Power Module
Current
(A)
Voltage Load
Regulation
(%)
Max Power
(W)
VDC %
IEPAS02 4.0
13.0
0.8
0.8
25.8
5.225
+15.2
-15.2
±
0.5
±
0.5
±
2.3
±
2.3
1.5
4
3
3
130
(max output
per power
module)
IEPAF02 4.0 25.8
±
0.5 1.5 102
Monitor
Voltage
(VDC)
Low Voltage
Trip Point
(Typical)
DC power 5
15
-15
24
4.76
14.30
-14.30
24.50
Auxiliary
voltage
24
48
125
21.8
43.7
114.0
Fan
Assembly
Current (ARMS)
Operating Inrush
IEFAN01
(120 VAC)
1.2 1.6
IEFAN02
(240 VAC)
0.6 0.9
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com