EasyManua.ls Logo

Basler BE1-11g - Page 430

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
418 9424200994 Rev N
Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 168. Record the
results.
Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.
Step 7: (Optional.) Repeat steps 1 through 6 for 59X-2, 59X-3, and 59X-4.
Pickup Verification (Vx Third Harmonic Mode)
Step 1: Use BESTCOMSPlus to send the operational settings in Table 169 to the BE1-11g. Reset all
targets.
Table 169. Operational Settings (Vx Third Harmonic Mode)
Setting
Value
BESTCOMSPlus Screen
Description
Aux VT Ratio
1
System Parameters, Sensing
Transformers
Sets auxiliary VT ratio to 1
Aux VT
Connection
AN
System Parameters, Sensing
Transformers
Sets auxiliary VT connection to
AN
Element Mode
Vx Third
Harmonic
Protection, Voltage,
Overvoltage (59X-1)
Enables 59X-1 function for Vx
Third Harmonic mode
Timing Mode
Definite
Protection, Voltage,
Overvoltage (59X-1)
Selects definite timings
59X-1 3RD
Enabled
Target Configuration, Targets
Enables Vx Third Harmonic
target for 59X-1
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 290.
Blocking is disabled.
OUT1 closes for 59X-1 Trip.
OUT2 closes for 59X-1 Pickup.
Fault recording is enabled.
Figure 290. BESTlogicPlus Settings (Vx Third Harmonic Mode)
Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send
the first row of test settings in Table 170 to the BE1-11g.
Table 170. Pickup Test Settings (Vx Third Harmonic Mode)
Pickup Setting
Time Delay
125 V
50 ms
75 V
50 ms
30 V
50 ms
Step 4: Prepare to monitor the 59X-1 function operation. Operation can be verified by monitoring OUT2
(see Figure 290).
Auxiliary Overvoltage (59X) Test BE1-11g

Table of Contents

Related product manuals