EasyManua.ls Logo

Basler BE1-11g - Page 546

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
534 9424200994 Rev N
despite a second 43-1 OFF to ON initiate signal while the duration timer was active. Figure 324
illustrates the timing relationship of the 43-1 switch and 62-1 timer.
Figure 324. One-Shot/Non-Retriggerable Mode
Step 6: (Optional.) Repeat steps 1 through 5 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.
Step 7: (Optional.) Repeat steps 1 through 6 for settings group 1, 2, and 3.
One-Shot/Retriggerable Mode
Step 1: Use BESTCOMSPlus to send the operational settings in Table 243 to the BE1-11g. Retain the
logic settings from Figure 321.
Table 243. Operational Settings (One-Shot/Retriggerable Mode)
Setting
Value
BESTCOMSPlus Screen
Description
62-1 Mode
One-
Shot/Retriggerable
Control, Logic Timers (62)
Sets 62-1 to One-
Shot/Retriggerable mode
62-1 Time
Delay 1 (T1)
15,000 ms
Control, Logic Timers (62)
Sets 62-1 pickup time delay to
15,000 ms
62-1 Time
Delay 2 (T2)
20,000 ms
Control, Logic Timers (62)
Sets 62-1 dropout time delay
to 20,000 ms
43-1 Mode
Pulse
Control, Virtual Control
Switches (43)
Sets 43-1 to Pulse mode
62-1 Target
Enabled
Target Configuration,
Targets screen.
Enables 62-1 target
Step 2: Step 4 supplies the 62-1 timer with a momentary initiate input by pulsing the 43-1 switch from
an OFF state to an ON state and then back to an OFF state. You can view the state changes of
the 43-1 switch at the Metering > Control > Virtual Switches screen on the front-panel display.
Step 3: Close communication with BESTCOMSPlus.
Step 4: Using the front-panel display, navigate to Metering > Control > Virtual Switches. Highlight the
first switch (43-1) and press the Right key on the front panel to enter the 43-1 control screen.
Use the Edit key to login. Highlight Operate and then press the Edit key to change the state of
the 43-1. Using the Up/Down keys select PUL and then press the Edit key.
Step 5: Repeat step 4.
Step 6: Wait at least 15 seconds (but no longer than 35 seconds) and then repeat step 4.
Step 7: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events
screen. Verify that approximately 15 seconds after the second 43-1 OFF to ON initiate signal,
the 62-1 timer output went true. Verify that the timer output went false when the third OFF to ON
initiate signal forced the 62-1 time delay 1 to restart. Figure 325 illustrates the timing
relationship of the 43-1 switch and 62-1 timer.
P0035-31
02-27-06
Block
Initiate
62-x
Logic Timers (62) Test BE1-11g

Table of Contents

Related product manuals