EasyManua.ls Logo

Basler DGC-2020 - Connections for Typical Applications

Basler DGC-2020
251 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9400200990 Rev I DGC-2020 LSM-2020 (Load Share Module) 8-9
LSM-2020
DGC-2020
Other
Devices
P0053-08
Engine
120 ohm
Termination
120 ohm
Termination
CAN-H
CAN-L
CEM-2020
(Optional)
Figure 8-5. CANBus Interface with DGC-2020 providing One End of the Backbone
Ethernet Port
The LSM-2020 has Ethernet capability. The LSM-2020 connects to a PC through a RJ-45 jack (J3).
Connections for Typical Applications
Figure 8-6 illustrates typical LSM-2020 connections.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Ethernet
LSM-2020
AVR+
AVR-
AVR’
GOV+
GOV-
GOV’
CANL
CANH
GND
V+
IN-
I+
LS+
LS-
LS’
B-
B+
GND
Voltage
Regulator
Analog
Aux
Input
Governor
Analog
Aux
Input
DGC-2020
CANL
CANH
SHIELD
To System Load
Share Line
12 or
24 Vdc
P0052-42
Figure 8-6. Typical LSM-2020 Connections
www . ElectricalPartManuals . com

Table of Contents

Related product manuals