B-8 DGC-2020 Modbus Communication 9400200990 Rev I
MAPPING - DGC 2020 PARAMETERS INTO MODICON ADDRESS SPACE
Table Conventions
Table B-3 uses the conventions outlined in this section.
The “Data Format” column uses the following abbreviations:
DP - Double Precision
TP - Triple Precision
FP – Floating Point
Data formatted in Double Precision uses a 2 register group designated (a) and (b) and is defined as
follows:
Register (a) - 2 hi-order bytes
Register (b) - 2 lo-order bytes
Data formatted in Triple Precision uses a 3 register group designated (a), (b) and (x). It is defined as
follows:
Register (a) - 2 hi-order bytes
Register (b) - 2 mid-order bytes
Register (x) - 2 lo-order bytes
Other register groups using the (a), (b), etc. designators are an ordered data group of consecutive ASCII
characters or data bytes.
Legacy Parameter Table
The DGC-2020 maps all legacy parameters previously associated with the DGC-500 and DGC-1000 into
the Holding Register address space (40000 to 41999). Query address N will access the Holding Register
N+1. The Data Format is Integer type data unless identified otherwise in the Data Format column.
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler DGC-2020 and is the answer not in the manual?

Basler DGC-2020 Specifications

General IconGeneral
BrandBasler
ModelDGC-2020
CategoryController
LanguageEnglish

Related product manuals