9400200990 Rev I DGC-2020 BESTCOMSPlus Software 4-21
Figure 4-18. Automatic Restart Settings
A
Auto Restart Enable: Enable or Disable.
B
Auto Restart Interval: Adjustable from 0.5 to 30 minutes in 0.5 minute increments.
C
Auto Restart Attempts: Adjustable from 1 to 10 in increments of 1.
Exercise Timer
The exercise timer is used to start the genset at a predetermined time and run for the user-defined period.
The mode
A
defines how often the genset will run. If monthly is selected, you must select the day of the
month
B
to start. If weekly is selected, you must select the day of the week
C
to start. Settings for Start
Hour
D
and Start Minutes
E
may also be defined. The Run Period Hours
F
and Minutes
G
define how long the
genset will run each time. If Run with Load
H
is enabled, the DGC-2020 will close its GEN breaker during
the RUN time.
Contact inputs and outputs can be assigned to the function. Refer to Section 5, BESTlogic+
Programmable Logic, for more information.
BESTCOMSPlus exercise timer settings (DGC-2020, System Parameters, Exercise Timer) are illustrated
in
Figure 4-19.
Figure 4-19. Exercise Timer Settings
A
Mode: Monthly, Weekly, or Daily.
B
Start Day Of Month: Adjustable from 1 to 31 in 1 day increments.
C
Start Day Of Week: Sunday, Monday, Tuesday, Wednesday, Thursday, Friday, or Saturday.
D
Start Hour: Adjustable from 0 to 23 in 1 hour increments.
E
Start Minute: Adjustable from 0 to 59 in 1 minute increments.
F
Run Period Hours: Adjustable from 0 to 23 in 1 hour increments.
G
Run Period Minutes: Adjustable from 0 to 59 in 1 minute increments.
H
Run with Load: Enable or Disable.