EasyManua.ls Logo

Basler DGC-2020 - Loss of Excitation Protection (40 Q)

Basler DGC-2020
251 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9400200990 Rev I DGC-2020 BESTCOMSPlus Software 4-37
power protection settings automatically switch from the three-phase settings to the single-phase reverse
power protection settings. The 32 element monitors three-phase real power when three-phase sensing is
active or single-phase real power if single-phase sensing is active.
When the total wattage in the tripping direction (generator absorbing power) is greater than the pickup
setting
A
for the duration of the 32 activation delay setting
B
, a reverse power condition is annunciated. A
reverse power annunciation can be user-selected to trigger a pre-alarm
C
(warning) or alarm
C
(shutdown).
A reverse power annunciation can also be user-configured to close a programmable output.
The hysteresis setting
D
functions as a reverse power dropout by preventing rapid switching of the pickup
output.
BESTCOMSPlus reverse power protection settings (DGC-2020, Generator Protection, Reverse Power)
are illustrated in
Figure 4-34.
Figure 4-34. Reverse Power Protection Settings
A
Pickup: -50% to 5% of rated watts in 0.1% increments.
B
Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments.
C
Alarm Configuration: None, Alarm, or Prealarm.
D
Hysteresis: Adjustable from 1% to 10% in 0.1% increments.
Loss of Excitation Protection (40Q)
Two sets of loss of excitation settings are provided: one for three-phase generator connections and one
for single-phase generator connections. The pickup setting
A
entered is based on the CT secondary side
(DGC-2020). When a single-phase override contact input is received by the DGC-2020, the loss of
excitation protection settings automatically switch from the three-phase settings to the single-phase loss
of excitation protection settings.
When a generator’s excitation power is lost, the generator acts as a large inductor. The generator begins
to absorb large quantities of vars. The 40Q acts on the principal that if a generator begins to absorb vars
outside of its steady state capability curve, it has likely lost its normal excitation supply. The 40Q monitors
three-phase reactive power when three-phase sensing is active or single-phase reactive power if single-
phase sensing is active. It compares the reactive power to the 40Q response curve defined by the 40Q
pickup setting. Refer to
Figure 4-35.
www . ElectricalPartManuals . com

Table of Contents

Related product manuals