9400200990 Rev I DGC-2020 Modbus Communication B-9
Table B-3. Legacy Parameter Table
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
40001-18 RESERVED
PARAMETER SETTINGS
40019 Emergency Stop 0-1 W
0 =Off
1 =Stop
40020 Remote Start / Stop 0-1 W
0 =Stop
1 =Start
40021-22 RESERVED
SYSTEM PARAMETERS
40023 Default Generator Connection 0-2 R W
0=3ph L-L
1=3ph L-N
2=1ph A-B
40024 NFPA Level 0-2 R W
0=Off
1=Level 1
2=Level 2
40025 RESERVED
40026 Rated Engine RPM 750-3600 R W RPM
40027 Number Flywheel Teeth 50-500 R W
40028 Genset KW Rating 25-9999 R W KWatt
40029 No Load Cool Down Time 0-60 R W Minutes
GENERATOR PT PRIMARY
40030 Voltage(a) 1-15000 R W DP VoltsAC x10000
40031 Voltage(b) R W DP VoltsAC
GENERATOR PT SECONDARY
40032 Voltage 1-480 R W VoltsAC
GENERATOR CT PRIMARY
40033 Current 1-5000 R W AmpsAC
LOW FUEL ALARM
40034 Enable 0-1 R W
0 =Off
1 =On
40035 Threshold 2-50 R W % Full Tank
LOW FUEL PRE-ALARM
40036 Enable 0-1 R W
0 =Off
1 =On
40037 Threshold 10-100 R W % Full Tank
LOW COOLANT TEMP PRE-ALARM
40038 Enable 0-1 R W
0 =Off
1 =On
40039 Threshold 32-150 R W Degrees F
BATTERY OVERVOLTAGE PRE-ALARM
40040 Enable 0-1 R W
0 =Off
1 =On
40041 RESERVED
MAINTENANCE INTERVAL PRE-ALARM
40042 Enable 0-1 R W
0 =Off
1 =On
40043 Threshold 0-5000 R W Hours
ENGINE KW OVERLOAD PRE-ALARM
40044 Enable 0-1 R W
0 =Off
1 =On
40045 Threshold 95-140 R W % of Rated
HIGH COOLANT TEMP PRE-ALARM
40046 Enable 0-1 R W
0 =Off
1 =On
40047 Threshold 100-280 R W Degrees F
LOW OIL PRESSURE PRE-ALARM
40048 Enable 0-1 R W
0 =Off
1 =On