B-10 DGC-2020 Modbus™ Communication 9400200990 Rev I
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
40049 Threshold 3-100 R W PSI
LOW BATTERY VOLTAGE PRE-ALARM
40050 Enable 0-1 R W
0 =Off
1 =On
40051 Threshold
60-120 (12V)
120-240 (24V)
R W .1 Volts DC
40052 Pre-alarm Activation Time Delay 1-10 R W Seconds
WEAK BATTERY VOLTAGE PRE-ALARM
40053 Enable 0-1 R W
0 =Off
1 =On
40054 Threshold
40-80 (12V)
80-160 (24V)
R W .1 VoltDC
40055 Pre-alarm Activation Time Delay 1-10 R W Seconds
40056-59 RESERVED
HIGH COOLANT TEMP ALARM
40060 Enable 0-1 R W
0 =Off
1 =On
40061 Threshold 100-280 R W Degrees F
40062
Arming Delay after Crank
Disconnect
60 R W Seconds
LOW OIL PRESSURE ALARM
40063 Enable 0-1 R W
0 =Off
1 =On
40064 Threshold 3-100 R W PSI
40065
Arming Delay after Crank
Disconnect
5-15 R W Seconds
OVERSPEED ALARM
40066 Enable 0-1 R W
0 =Off
1 =On
40067 Threshold 105-140 R W % of Rated
40068 Alarm Activation Time Delay 0-500 R W MilliSec
40069-71 RESERVED
CRANKING PARAMETERES
40072 Cranking Style 0-1 R W
0=Contin.
1=Cycle
40073 Number of Crank Cycles 1-7 R W
40074 Cycle Crank Time 5-15 R W Seconds
40075 Continuous Crank Time 1-60 R W Seconds
40076 Crank Disconnect Limit 10-100 R W % of Rated
40077 Pre-crank Delay 0-30 R W Seconds
SYSTEM MONITOR
40078 Remaining Cooldown Time 0-60 R - Minutes
40079 RESERVED
40080 Active Speed Signal Sources 1-4 R -
1=MPU
2=ALT
3=GEN
4=NONE
40081 Sender Failure Alarm Code
individual bits
are 0 or 1
R -
b0=High Coolant Temperature
b1=Oil Pressure
b2 Fuel Level
b3=Generator Voltage Sensing
b4=Magnetic Pick-up
b5-b7 not used