4-30 DGC-2020 BESTCOMSPlus Software 9400200990 Rev I
Figure 4-27. Pre-Alarms Configuration
A
High Fuel Level: Enable or Disable, threshold is adjustable from 0 to 100% in 1 % increments.
B
Low Battery Voltage: Enable or Disable, threshold is adjustable from 6 to 12 Vdc (12 Vdc battery) or 12
to 24 Vdc (24 Vdc battery) in 1 Vdc increments. Activation delay is adjustable from 1 to 10 s in 1 s
increments.
C
Weak Battery Voltage: Enable or Disable, threshold is adjustable from 4 to 8 Vdc (12 Vdc battery) or 8
to 16 Vdc (24 Vdc battery). Activation time delay is adjustable from 1 to 10 s in 1 s increments.
D
Battery Overvoltage: Enable or Disable, threshold is adjustable from 12 to 32 Vdc in 0.1 increments.
E
Maintenance Interval: Enable or Disable, threshold is adjustable from 0 to 5,000 h in 1 h increments.
F
Engine kW Overload: Enable or Disable, threshold is adjustable from 95 to 140% of Genset kW Rating
in 1% increments.
G
Low Fuel Level: Enable or Disable, threshold is adjustable from 10 to 100% in 1 % increments.