Example:
Product: Gasoline rho = 0.7 g/cm
3
Cylindrical container: d = 1200 mm
inside
Source: Co-60
HVL = 0.7 x 1200 / 157 = 5.4
Always round down result!
Input in code 39: 5
Example:
Product: Coal rho = 0.5 g/cm
3
Container diameter:
d = 1500 mm inside
Source: Cs-137
HVL = 0.5 x 1500 / 110 = 6.8
Always round down result!
Input in code 39: 6
The calibration of bulk cone measurements switching at a certain
bulk cone diameter is described on page 62.
As an alternative to code 39, you may also use - in the profes-
sional mode - the bulk density function in code 35.
Interference radiation detection
Enable / Disable interference radiation detection
(Only in the professional mode)
Interference radiation detection
This function detects interference radiation if the live count rate
exceeds the empty count rate in code 30 by a factor of 1.5. If in-
terference radiation has been detected, the measurement is
stopped for at least the length of the waiting time defined in code
41. For further information see page 64.
Bulk density:
0.5 (g/cm³)