D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 12
Bosch Security Systems | 5/05 | F001U003636B
Phone Supv Time
Default: Blank
Selection:
Blank or 10 to 240
Blank No phone line supervision.
10 to 240 Enter the number of seconds (in 10
second increments) you wish to
supervise the phone line. After a
faulted phone line restores, it takes the
same amount of time to start restoral
responses.
Phone line trouble responses: Keypads display
SERVC PH LINE # to indicate which phone line
failed. The keypad initiates a trouble tone if
Buzz on
Fail
is Yes and
CC Trouble Tone
is Yes.
With dual phone lines (using the D928 Module), the
restored phone line handles all messages regardless of
the phone line’s number.
Phone, Trouble, and Restoral Events report when they
occur. They report also when a Diagnostic Report is
initiated from a keypad or by a Sked.
Alarm On Fail
Default: No
Selection:
Yes or No
Yes Generate alarm responses when a
phone line fails.
No Phone failures report as trouble
responses for Area 1 or the account
number associated with Area 1.
Phone Supv Time must be programmed to
use this feature.
Phone Failure Alarm Responses: The Alarm Bell
relay for Area 1 activates. All Phone Event messages
report as Area 1 and the account number for Area 1.
Buzz on Fail
Default: No
Selection:
Yes or No
Yes Generate panel-wide trouble tones and
display PHONE FAIL # at keypads
when a Phone Fail Event occurs.
No Does not generate trouble tones at
keypads when a Phone Fail Event
occurs. PHONE FAIL # still displays.
Phone Supv Time must be programmed to
use this feature.
When
Buzz on Fail
is Yes, users can disable the
resulting trouble tone on individual keypads by setting
CC# Trouble Tone
to No.
Two Phone Lines
Default: No
Selection:
Yes or No
Yes The D928 Dual Phone Line Module
is installed. The LEDs on the D928
light to indicate primary or secondary
line trouble and COMM FAIL.
No D928 Dual Phone Line Module is not
installed.
Program Phone Supv Time when using
two phone lines.
BFSK Duress Code
Default: 0
Selection:
0 to 9
If
Duress Enable
in Area Parameters is Yes and
Modem Format
in Phone Parameters is No, you must
program a number to identify Duress Reports at the
central station.