D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 26
Bosch Security Systems | 5/05 | F001U003636B
To eliminate AC Reporting, AC Tag Along
and AC Fail/Res Rpt must be programmed
as No and the second digit of the AC Fail
Time must be a 1, 2, 3, 4, 5, or 6.
AC Fail/Res Rpt
Default: No
Selection:
Yes or No
Yes Send AC Fail and AC Restoral
Reports.
No Does not send AC Fail and AC
Restoral Reports.
AC Power Supervision Reports are sent to the central
station and local printer at the time programmed for
AC Fail Time
.
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as No and
program AC Tag Along as Yes. AC
Restoral Reports are not sent.
AC Tag Along
Default: Yes
Selection:
Yes or No
Yes Send AC messages as tag along
events.
No Do not send AC messages as tag
along events.
Send AC Reports only if any other event occurs while
AC is off-normal.
If AC Tag Along is set to Yes and a
subsequent event is generated, the AC
Fail Event is sent first, before sending any
subsequent events.
AC Tag Along is required for NFPA and
UL 864 commercial fire systems. Be sure
to program AC Fail/Res Rpt as No if AC
Tag Along is programmed Yes.
AC/Battery Buzz
Default: No
Selection:
Yes or No
Yes Initiates panel-wide trouble tone at all
keypads.
No Does not initiate panel-wide trouble
tone at keypads
Initiates a panel-wide trouble tone at keypads when
AC fails or battery is low or missing. This program
item does not prevent the SERVC AC FAIL or SERVC
BATT LOW displays.
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as Yes.
De-selecting individual keypads for panel-
wide trouble tones: Panel-wide trouble
tones for programming the CC Trouble
Tone in the keypad parameters to No can
turn off individual keypads (based on their
CC# [1 to 8]).
Bat Fail/Res Rpt
Default: Yes
Selection:
Yes or No
Battery Failure and Restoral Reports are sent
to the central station. They are routed to the
telephone number programmed for
Power/Phone Events.
Modem
Reports
Missing or
shorted
Discharged
below 12.1
VDC
BATTERY
MISSING
BATTERY LOW
Yes
BFSK
Reports
Missing, shorted
low battery
TROUBLE
ZONE 9
No
Battery Failure and Restoral Reports are not
sent to the central station.
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as Yes.