D9412GV2/D7412GV2 | Program Entry Guide | 6.0 GV2AUX EN | 133
Bosch Security Systems | 5/05 | F001U003636B
Table 41: Cross Point Ranges Within Groups
Cross Point Group Point Range
1 1 to 8
2 9 to 16
3 17 to 24
4 25 to 32
5 33 to 40
6 41 to 48
7 49 to 56
8 57 to 64
9 65 to 72
10 73 to 80
11 81 to 88
12 89 to 96
13 97 to 104
14 105 to 112
15 113 to 120
16 121 to 127
17 129 to 136
18 137 to 144
19 145 to 152
20 153 to 160
21 161 to 168
22 169 to 176
23 177 to 184
24 185 to 192
25 193 to 200
26 201 to 208
27 209 to 216
28 217 to 224
29 225 to 232
30 233 to 240
31 241 to 247
When any Cross Point detects an alarm condition, the
control panel starts a timer as programmed in the
Cross Point Time
prompt.
If a second Cross Point within the same Cross Point
Group detects an alarm condition, the control panel
creates a Cross Point Alarm Event for both points,
provided both points activate inside the Cross Point
Window.
If a single Cross Point detects an alarm and stays
faulted throughout the Cross Point Window, a
standard Alarm Report is generated for that point.
Conversely, if a single Cross Point detects an alarm,
then restores, and no other conditions occur, an
Unverified Event is generated for that point. A second
alarm on the first point does not create an Alarm
Event but rather an Unverified Event.
Section 2.3 Routing on page 13 determines whether
these events are sent to a central station. An
Unverified Event does not produce a corresponding
Restoral Event.
The Cross Point function applies only to alarm
conditions. It does not apply to supervisory or trouble
conditions. Points programmed with point response D
(Delayed) eventually enter into an alarm condition if
the area is not disarmed in time.
Use the Cross Point function on Non-fire
points only.
Cross Point Time
Default: 20 seconds
Selection: 5 seconds to 255 seconds
Select the amount of time (in seconds) that points
within a Cross Point Group are in alarm before a
Cross Point event is generated.