4.4 COMMAND 7 and COMMAND 9
These entries assign point indexes, BFSK report code,
BFSK relay that activates, and the text for the
COMMAND 7 and COMMAND 9 keypad functions.
CMD7 Point Index
Default: 31
Selection: Blank (00) to 31
This entry selects one of the 31
P## Index
codes that
define how the control panel reacts when a
COMMAND 7 is initiated.
The point index code used for COMMAND
7 must not be used for any other points on
the system.
If the point index for COMMAND 7 has Fire
points programmed as Yes, this causes
access control doors to unlock if Fire
Unlock is also programmed as Yes. Refer
to the D9210B Program Entry Guide
(P/N: 32206).
CMD7 BFSK/Relay
Default: 1
Selection: 0 to 9
This entry selects one of the digits shown for reporting
in BFSK or for activating relays 73 to 80 (on the
D9412GV2) or relays 9 to 16 (for the D7412GV2)
when COMMAND 7 is initiated (refer to the
P###
BFSK/Relay
prompt in Section 4.3 Point Assignments on
page 94).
COMMAND 7 does not activate the
Summary Fire Alarm relay.
CMD7 Point Text
Default: [COMMAND][7]
Selection:
Up to sixteen alphanumeric
characters
Enter alphabetic characters A to Z in capital letters
Enter up to sixteen characters of text to describe the
point. This point text appears at keypads (if the point is
programmed as visible) and sent to the D6500 or
D6600 when transmitting in Modem IIIa
2
format (if it
is a reporting point).
CMD9 Point Index
Default: 31
Selection: Blank (00) to 31
This entry selects one of the 31
P## Index
codes that
define how the control panel reacts when a
COMMAND 9 is initiated.
The point index code used for COMMAND
9 must not be used for any other points on
the system.
If the point index for COMMAND 9 has Fire
points programmed as Yes, this causes
access control doors to unlock if Fire
Unlock is also programmed as Yes. Refer
to the D9210B Program Entry Guide
(P/N: 32206).
CMD9 BFSK/Relay
Default: 1
Selection: 0 to 9
The value in this entry selects one of the digits shown
for reporting in BFSK or for activating relays 73 to 80
(on the D9412GV2) or relays 9 to 16 (for the
D7412GV2) when a COMMAND 9 is initiated (refer
to the
P### BFSK/Relay
prompt in Section 4.3 Point
Assignments on page 94).
COMMAND 9 does not activate the
Summary Fire Alarm relay.
CMD9 Point Text
Default: [COMMAND][9]
Selection:
Up to sixteen alphanumeric
characters
Enter alphabetic characters (A to Z) in capital letters
Enter up to sixteen characters of text to describe the
point. This point text is displayed at keypads (if the
point is programmed as visible) and sent to the
D6500/D6600 when transmitting in Modem IIIa
2
format (if it is a reporting point).