D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 46
Bosch Security Systems | 5/05 | F001U003636B
CC# Supervised
Default: Refer to the program record sheet
Selection:
Yes or No
Yes Only one keypad can be installed for this CC
SDI address.
No More than one keypad can be installed using
this CC SDI address with the same address
DIP switch setting.
Supervise this SDI address and generate Trouble SDI
Reports and local trouble annunciation if a problem
occurs with this keypad or the SDI bus.
Keypads that share the same address
setting display the same text and emit the
same tones, regardless of which keypad’s
keys are pressed.
Trouble SDI # Reports are always reported
as Area 1, Account 1 Events regardless of
the area the SDI device is assigned.
When this prompt is Yes, you cannot have
duplicate DIP switch settings.
When a D1260 Alpha V Keypad is
assigned to a keypad address, you must
program CC# Supervised as Yes.
CC# Area Assign
Default: 1
Selection:
1 to 8
Blank is not a valid entry.
Enter the area number where you are installing this
keypad or keypads with this address and the same DIP
switch settings.
CC# Scope
Default: Refer to the program record sheet
Selection:
Panel Wide, Custom, No Keypad,
Area, and Account
Panel
Wide
A panel-wide keypad can view
information and perform Arming and
Disarming functions for all areas in the
control panel. A panel-wide keypad
can cross account boundaries. This is
normally used with a master area.
Account An Account keypad can view
information, and perform Arming and
Disarming functions for all areas with
the same
A# Acct Number
, in Area
Parameters. This is normally used for
an associate area.
Area An area keypad is restricted to viewing
information and Arming or Disarming
functions for the area to which it is
assigned.
Custom A custom keypad has no keypad
restrictions.
No
Keypad
No keypad installed at this address.
CALL FOR SERVICE display shows,
indicating the control panel is not
polling this address.
This program item is used to define the areas affected
when an arming command is executed on this keypad,
the areas this keypad can view, and the areas to which
this keypad can move.
Press the [SPACE] bar to scroll through the selections.
Press [ENTER] when the correct selection appears in
the display.
In applications where keypads include more
than one area, active alarms in remote
areas must be acknowledged before
arming or disarming the local area.
The following prompts are visible only
when you program CC## Scope to
Custom. If you change the keypad scope
selection to Custom from Panel Wide,
Account, or Area, the settings from the
previous CC# Scope selection become the
default settings for the custom parameters
in CC# A1 [through A8] in Scope. Before
exiting a custom program, check each area
and ensure that it is enabled and disabled
correctly.