D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 95
Bosch Security Systems | 5/05 | F001U003636B
P### Point Index
Default: Refer to the program record sheet
Selection: Blank (00) to 31
This entry selects one of the 31
P## Index
codes that
define the point’s characteristics and determines how
the control panel responds to various point conditions.
Blank (00) disables the point.
Missing Point Report
If a Point Index is assigned to a point that has an
incorrect address or that is not connected to the point
bus, a Missing Point Report occurs.
When a POPIT is missing, the control panel generates
the following responses based on the point type:
• Fire points generate missing trouble responses.
• Non-fire 24-hour points generate missing alarm
responses.
• Non-fire, non 24-hour points generate missing
alarm responses while armed, and trouble
responses while disarmed. Exception: Non-fire,
non-24-hour points with a point response of 9 to D
generate a missing alarm response while disarmed.
POPIT modules monitor their sensor loops for three
conditions: loop normal, loop open, and loop shorted.
They send reports on these three conditions to the
control panel. The control panel uses point
programming to interpret the sensor loop information
sent by the POPITs and to make the appropriate
system response.
P### Area Assign
Default: 1
Selection: 1 to 8
The areas are numbered 1 to 8. Select the area number
to which the point is assigned.
P### Debounce
Default: 2
Selection: 1 to 15
1 .300 seconds
2 .600 seconds
3 .900 seconds
4 1.2 seconds
5 1.5 seconds
6 1.8 seconds
7 2.1 seconds
8 2.4 seconds
9 2.7 seconds
10 3.0 seconds
11 3.3 seconds
12 3.6 seconds
13 3.9 seconds
14 4.2 seconds
15 4.5 seconds
The debounce count is the number of times the control
panel scans a point before generating an alarm. Scan
cycles are 300 ms.
For appropriate settings consult the manufacturer’s
instructions for the device connected to this point.
Use an entry of two or higher. Interior
Follower points need a Debounce value of
at least three.
Door points assigned to D9210B modules