D9412GV2/D7412GV2 | Program Entry Guide | 6.0 GV2AUX EN | 124
Bosch Security Systems | 5/05 | F001U003636B
Figure 8: Com Port Selection within HyperTerminal
Figure 9: External Modem Connection
P3
P2
1 2 4 8
SER RX TX RX TX BUS
SDI
PWR
SDI
A
SDI
B
SDI
COM
D9133DC
EART H GROUND
COMMON
BATTERY NEGATIVE ONLY
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 6 0 Hz
Model D1640
Internally Fused - Do not shor t
Requ ires Unswitc hed Outlet
Do not share with other equipment
GROUND FAULT DETECT
Ena bled
Disabled
PHONE
LED
ON when
communicating
OFF when idle
Digital Alarm Communicator Transmitter
WAR NIN G!
Multi-Battery installat ion requires
Model D122 Du al Battery Harness.
Improper installation can be a fire
hazard.
Battery: Replace every 3 to
5 years with Model D126, 12 V
7 Amp Hr Lead Acid Battery
D9412GV2 Control/Communicator is UL Listed For Cent ral Station, Local, Remote Station and
Household Fire Alarm, and Central Station, Local, Police Station Connect, Household Burglar Alarm
and Encrypted Line Security when communicating via a network.
System is int ended to be checked by a Q ualified Technician a t least every 3 years.
The types of initiating circuits the panel has been approve d for are A, M, W, SS.
VOLTA GE R ANG ES
Open 3.7 - 5.0 VDC
Norma l 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
GRN
Reset Pin
Disab le all except Batte ry
Charging and Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW D ATA BUS A
GREEN DATA BUS B
BLACK C OMMON
ZONEX OUT 1
ZONEX IN 1
N.F.P.A.
Style 3. 5
Sign aling
Line
Circuits
D5200
PROG CONN
F01U003643B
Point 8
S3 Option
1211 13
Point 1 Point 2
1514 16
Point 3 Point 4
1817 19
Point 5 Point 6
2120 22
Point 7 Point 8
LEDs Off When Normal
Charging Status
Low Battery - 12.1 VDC
YEL
RED
10.2 VDC - Battery Load S hed
This equipme nt should be installed in accordance w ith the NFPA 70 (Natio nal Electrical Code)
and NFPA 72 (Nat ional Fire Alarm Cod e) for Local, Central Station, Remote Station , Proprietary and
Household Fire Warning Systems and under the limits of the Local Authority Having Jurisdiction
(National Fir e Protection As sociation, Ba ttermarch Park, Q uincy, MA 02269) . Printed inform ation
describing proper installation, operation, testing, maintenance, evacuation planning and repair
service is to be provided with t his equipment.
D9412GV2
26
25
ZONEX POWER +
24
ZONEX COMMO N
23
PHONE LINE SEIZED
Closed = 1K
EOL
Normal Operation
Open =AB-12 UL
Bell Box 22 0 K
TIP
RING
TELCO CO RD
MODEL D 16 1
SDI Connector
ZONEX OUT 2
ZONEX IN 2
Refe r to D94 12GV2/D7 412GV2 Appr oved Ap plicatio ns Compli ance Gui de (P/N: F01U003 639___)
For S ystem Wir ing Dia gram, Issu e A
Refe r to D94 12GV2/D7 412GV2 Appr oved Ap plicatio ns Compli ance Gui de (P/N: F01U003 639___)
For Compatible Smoke D etectors
POWER SUPPLY REQUIREMENTS
The Power Sup ply provides a maximum of 1.4 Amps for t he Control Panel and all
Accesso ry Devi ces. For System Loading , refer to D9412 GV2/D741 2GV2
Operat ion and Instal lation Guide (P /N: F01U003 641___).
(P/N: F0 1U003641) for Power Requ irements relating to Terminals 6 and 7 .
CAUTION: See D9 412GV2/D 7412GV2 Opera tion and Instal lation Guide
All ext ernal c onnection s except Terminal 5 (ba ttery po sitive) are in herently p ower
limited . Requi rements for batter y standby time might redu ce allo wable ou tput.
CAUTI ON: Avoid damage to Panel.
Do not connect 24 V to terminals.
Maximum ch arging curr ent 1.4 A
PROGRAMMABLE
ALARM OUTPUT S
Ter min al s
SWITCHED AUX
and
67
Term ina l
8
1 - Remote Programming Software (RPS)
2 - Modem
3 - PSTN
4 - D9412GV2/D7412GV2 Control Panel
5 - Standard serial cable
6 - SDI bus