D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 59
Bosch Security Systems | 5/05 | F001U003636B
User Cmd 9
Default: P
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
24 User COMMAND
9
[COMMAND][9]
Use this function to activate an alarm programmed in
COMMAND 9 in the RADXPNTS Handler.
Bypass a Pt
Default: P
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
25 Bypass a Point [COMMAND][0]
Use this function to bypass individual points that have
P## Bypassable
enabled. Points within the scope of
the keypad can be bypassed where the function is
entered (refer to Section 2.10.1 Keypad (Command Center)
Assignment) on page 45.
The control panel ignores alarms and troubles, and
does not display point faults when a point is bypassed.
Unbypass a Pt
Default: P
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
26 Unbypass a Point [COMMAND][0][0]
Use this function to unbypass individual points that are
programmed either
P## FA Retrnable
or
P##
Bypass Returnable
. Points within the scope of the
keypad can be unbypassed where the function is
entered (refer to Section 2.10.1 Keypad (Command Center)
Assignment) on page 45. The control panel responds to
alarms and troubles, and displays point faults when a
point is unbypassed.
Reset Sensors
Default: E
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
27 Reset Sensors [COMMAND][4][7]
Use this function to activate the Reset Sensors function
for Fire or Intrusion points programmed as
P##
Resettable
in Section 4.1 Point Index on page 81. Points
within the scope of the keypad where the function is
entered reset. Refer to Section 2.10.1 Keypad (Command
Center) Assignment on page 45.
Change Relay
Default: P
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
28 Change Relays [COMMAND][5][4]
Use this function to manually set and reset Relays 1
through 128 (1 through 64 in a D7412GV2) that are
installed in the system.
Remote Program
Default: P
Selection:
Blank, E, or P
Function No. Function Name Alternate Keystroke
29 Remote
Programming
[COMMAND][4][3]
Use this function to start remote programming
software (RPS) sessions. When the phone is ringing at
the control panel, starting this function causes the
control panel to seize the line.