D9412GV2/D7412GV2 | Program Entry Guide | 4.0 RADXPNTS EN | 86
Bosch Security Systems | 5/05 | F001U003636B
P## Pt Response
Default: Refer to the program record sheet
Selection: 0 to F
Controlled (Non-24-Hour Points)
Point Response 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open
I I I I D D I I D I I I I I T
Armed Short
I I I I I I D D D I I I I I I
Disarmed Open
T T T I I T I T
Disarmed Short
T T T I T I I
24-Hour Points
Point Response 0 1 2 3 4 5 6 7 8 9 A B C D E F
Open I T I T I T S T S S
Short I I T T I T T S S S
Key: I = Instant alarm
D = Delayed alarm
T = Trouble
S = Supervisory
Blank = Audible or visual response
Example of Controlled point:
Point Type = 1
Point Response = 8
Perimeter point with delayed alarm response when
armed (opened or shorted) and no response when
disarmed.
Example of 24-hour point:
Point Type = 0
Point Response = 8
24-hour point with supervisory response when open
and a trouble response when shorted.
When programming the point response for
Inovonics Wireless Transmitters,
regardless of how the transmitter is
programmed, the D8125INV Wireless
Interface always sends the off-normal state
to the control panel as a short and a
tamper condition as an open. As a result,
typical point responses for the Inovonics
transmitters would include 0, 1, 6, 7, and E
for controlled points, and 0 and 1 for 24-
hour Burg points. When programming a
transmitter as a Fire point, use a point
response of 1.
Wireless transmitters are not UL Listed
with the D9412GV2/D7412GV2 in fire or
burglary applications. Inovonics Wireless
Transmitters, when used with the
D8125INV Wireless Interface on a
9000GV2 Series control panel, are not UL
Listed for use with fire or burglary
applications.
With Supervisory Pt Response
(S = Supervisory), the BFSK format does
not transmit fire supervisory or Non-fire
Supervisory Events. Modem format must be
used with Supervisory Point Responses.