D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 75
Bosch Security Systems | 5/05 | F001U003636B
Comm Fail
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when a control panel cannot communicate a
report after making ten attempts to each routing
destination. At the same time, COMM FAIL RT ##
displays at the keypad. This relay automatically resets
when a report is sent successfully.
Use this relay to report primary digital
report failure to an alternate communication
device.
Log % Full
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Enter the number of the relay that activates when the
log reaches the programmed percentage of its capacity
as programmed in RPS Parameters program item Log
% Full. This relay provides a steady output until a Get
Log and Set Pointer is executed from the remote
programming software (RPS).
Summary Fire
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Enter the number of the relay that activates when any
Fire point in the system (
P## Type 0
,
P## Fire
Yes)
enters into alarm. This relay provides a steady output
until all Fire points in the system return to normal.
Summary Alarm
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Enter the number of the relay that activates when a
Non-fire point enters into alarm. This relay provides a
steady output until the alarm is acknowledged by a
valid pass code, then cleared from alarm memory with
an acknowledgment at the keypad.
This relay does not activate for silent and
invisible alarms.
Summary Fire Tbl
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when any Fire point in the control panel is in
trouble, or if a Fire Supervision point is missing. This
relay provides a steady output until all Fire points
restore to a normal condition.
Summary SupFire
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when any Fire Supervisory point in the
control panel is in a supervisory condition (off-normal).
This relay provides a steady output until all Fire
Supervisory points are restored to a normal condition.
Summary Trouble
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when any Non-fire point in the control panel
is in a trouble condition. This relay provides a steady
output until the user at the keypad acknowledges the
trouble.
Summary SupBurg
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when any Non-fire Supervisory point in the
control panel is in a supervisory condition, or if a
Supervisory Burg point is missing. This relay provides
a steady output until the user at the keypad
acknowledges the condition.