D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 48
Bosch Security Systems | 5/05 | F001U003636B
CC# Assign Door
Default: Blank
Selection:
1 to 8, Blank
Blank No door controller is assigned for adding
tokens or the CLOSE DOOR # appears on
the keypad.
1 to 8 Assign the door controller that enters the
Add User Mode when initiated. If the
assigned door remains open and this keypad
has the
CC# Close Door Warning Tone
set to Yes, the CLOSE DOOR # message
appears on this keypad.
Program the door number used by this keypad to add
tokens or cards and to show CC Close Door.
If a door is not programmed for this
prompt and a door is not assigned to
the area using the D# Entry Area in the
RADAXS handler, IMPORTANT! 9210
NOT READY appears at this keypad
when you attempt to add a user. The
message indicates that the control panel
cannot start the Add User Mode until a
door is assigned to this keypad.
Assigning a door to a keypad is not
necessary for the user to control the
door(s) using the Door Control function.
Any door that is active can be controlled
by a user who has the appropriate door
control authority. The door control
functions are available to a valid user at
any keypad with access to the area
where the door is assigned.
During the Add User Mode, tokens or
cards, door control requests, and RTE/REX
do not function. Put the Door Mode into an
unlocked state before adding users if there
is heavy activity for this door.
CC# Trouble Tone
Default: Yes
Selection:
Yes or No
Yes Panel-wide trouble tones sound and
visual displays show at this keypad.
No Panel-wide troubles do not sound.
Visual displays still show.
Determines whether this keypad, or any keypad with
the same address setting, emits the panel-wide trouble
tones (power, phone, SDI bus, and Zonex bus).
Panel-wide trouble tones do not include
Point Troubles, Buzz on Fault, or Close
Door Now.
Assign two CCs to the same area so one
keypad emits the tone and another does
not.
CC# Entry Tone
Default: Yes
Selection:
Yes or No
Yes This keypad sounds entry tones.
No This keypad does not sound entry
tones.
Determines whether this keypad, or any keypad with
the same address setting, emits the Disarm Now entry
delay tone. Any Delay point within the area scope of
this keypad starts the entry sequence.
This prompt allows you to manage the tone
by keypad. Entry Tone can also be turned
off when programming your P## Entry
Tone off in Point Index.
Assign two CCs to the same area so one
keypad emits the tone and another does
not.