D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 73
Bosch Security Systems | 5/05 | F001U003636B
A# Force Armed
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This relay activates when this area is Force Armed. It
remains active until the area disarms or the control
panel resets.
If Force Bypassing is required during
Perimeter Arming, this relay does not
activate.
A# Watch Mode
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This relay activates when a Controlled point
programmed for
P## Watch Point
is faulted in the
specified area while the area is in Watch Mode and the
point is not armed. It remains active for 2 seconds
after each point is faulted.
A# Area Armed
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This relay activates when the specified area becomes
Master Armed. The exit delay must expire before the
relay activates. The relay remains active until the area
disarms. It does not deactivate during the entry delay
time.
If multiple areas use the same relay, the relay activates
when all areas are armed. It deactivates when the first
area disarms.
The
A# Area Armed
relay function can provide
visual feedback at a key switch station. Attach a LED
to the output of a D8129 Module programmed for this
function.
Programming a 64 in the Silent Alarm relay
for Area 8 causes the A# Area Armed
relay to activate at the beginning of the exit
delay time.
A# Area Fault
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates whenever a controlled (
P## Type 1, 2, 3
only) Perimeter or Interior point is faulted. The relay
remains active until all Perimeter and Interior points in
the area are normal.
Keyswitch area armed status with LEDs:
Use a D8129 Module and connect an LED
to indicate that the area is not ready to arm.
A# Duress Relay
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when a Duress alarm is generated from a
keypad assigned to the specified area.
Burg Time needs a bell period programmed
and A# Duress Enable must be Yes. This
relay activates when the Burg Bell starts
and deactivates when the Burg Bell time
ends. The Burg Bell pattern has no effect
on this relay function.
A# Perim Fault
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when a Controlled Perimeter point (
P##
Type 1
) assigned to the specified area is faulted,
regardless of the armed state of the area. This relay
provides a steady output until all Perimeter points in
the area return to normal.
This relay does not activate on interior
faults. To detect all area point faults,
program all points as Perimeter points in
the area where this relay is assigned.
A# Silent Alarm
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
This relay activates when a point assigned to the
specified area and programmed for
P## Silent Bell
goes into alarm.