D9412GV2/D7412GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 47
Bosch Security Systems | 5/05 | F001U003636B
CC# A1[through A8] in Scope
Default: Refer to the preceding important
note
Selection:
Yes or No
Yes Include this area in the scope of this
keypad.
No Do not include this area in the scope
of this keypad.
Determines whether any of the eight areas (Area 1 to
Area 8) and Doors (Door 1 to Door 8) are included in
the scope of this keypad for viewing status, arming or
disarming, and controlling doors from the keypad.
CC# Entr Key Rly
Default: Blank
Selection:
1 to 128, A, B, C, and Blank
Blank The [ENTER] key is not used to
activate a relay.
1 to 128,
A, B, C
Assign the relay number that activates
when [ENTER] is pressed at this
keypad after the user enters a valid
pass code.
Enter Key Relay: Program the relay number that
activates momentarily for 10 seconds when a user
enters a valid pass code and presses the [ENTER] key
on the keypad. Two events are generated when this
function is used: RELAY ### SET with User ID, and
RELAY ### RESET without User ID. The system
logs this action as two events.
• Entering a valid code and pressing [ENTER]
silences a ringing bell.
• Using
CC# Entr Key Rly
for a low-level access
control strike on a door does not shunt a point.
When programmed to activate a relay, the
[ENTER] key cannot be used for any other
function.
Relays used for this function must not be
shared with any other point, sensor reset,
control panel, or bell functions. Sharing can
cause errors in relay operation.
CC# Entr Cycl Dr
Default: No
Selection:
Yes or No
Yes The [ENTER] key is used to cycle the
door programmed for CC Assign
Door.
No The [ENTER] key is not used to cycle
the door.
Enter Key Cycle Door: Program this prompt as Yes
to start the door cycle sequence for the door number
programmed in
CC# Assign Door
when a user enters
a valid pass code and presses [ENTER]. This includes
shunting the point assigned to the door. ACCESS
GRANTED prints on the local printer and at the central
station receiver, if programmed.
• The service pass code cannot be used
for the CC# Entr Cycl Dr application.
• When programmed to activate a relay,
the [ENTER] key cannot be used for any
other function.
• Relays used for this function must not
be shared with any other point, sensor
reset, control panel, or bell functions.
Sharing can cause errors in relay
operation.
• The door does not cycle if Entr Key Rly
is programmed.
• 9210 NOT READY appears at this
keypad when you press [ENTER] if the
D9210B is not programmed with a D#
Entry Area (in the RADAXS handler) or
if CC Assign Door does not have a door
number assigned.