D9412GV2/D7412GV2 | Program Entry Guide | 7.0 RADXAXS EN | 139
Bosch Security Systems | 5/05 | F001U003636B
D# Deact On Open?
Default: Yes
Selection: Yes or No
Yes
Strike deactivates when the door is
opened after a valid Access Granted
request.
No
Strike remains activated for the
amount of the programmed strike
time whether door is opened or
closed.
Determines if the strike deactivates immediately upon
physically opening the door.
In order for this function to work, a point
needs to be assigned to the door.
To Reduce False Alarms, maintain D#
Deact on Open? as the default (Yes). This
helps prevent the door from bouncing open
and causing a false alarm.
D# RTE Shunt Only?
Default: No
Selection: Yes or No
Yes
Programmed shunt time activates so
door can be manually opened.
No
RTE automatically activates the
programmed strike and shunt time.
Use this program item to disable the strike, but still
activate the programmed shunt time at a Request to
Exit (REX) area.
Use this parameter when a user can open
a door manually without relying on a token
or card to activate the strike (such as with
a push bar).
When RTE Shunt Only is Yes, RTE Events
are not logged, reported, or printed.
D# REXShunt Only?
Default: No
Selection: Yes or No
Yes
Programmed shunt time activates so
the door can be manually opened.
No
REX automatically activates the
programmed strike and shunt time.
Use this program item to disable the door strike, but
activate the programmed
D# Shunt Time
upon a
request to exit (REX) from an area.
Use this parameter when a user can open
a door manually without relying on a token
or card to activate the strike (such as with
a push bar).
When REXShunt Only is Yes, REX Events
are not logged, reported, or printed.
7.3 Event Profile
This programming category is used to determine if
events are created for:
Access Granted and Access Denied
Door Requests
Door state changes due to manual (keypad) or
automatic scheduled or armed state changes
(skeds/hold open on disarm, normal on armed)
operation.
Door #
Default: 1
Selection: 1 to 8
Enter the door you plan to program.
RTE Events require Access Granted to be
programmed as Yes.