Type 8692, 8693
english
PROFIBUS-DP
1 GENERAL INFORMATION
The following sections of the general operating instructions do not apply to the positioner with PROFIBUS-DP:
Variants of the positioner
Initial start-up
Electrical connection
Specifying the standard settings
Function INPUT
Function SPLTRNG
Function BINARY-IN
Function OUTPUT
Function CAL.USER / calibr. INP
Function CAL.USER / calibr. SP
2 TECHNICAL DATA
The protocol sequence complies with the standard DIN 19245 Part 3.
GSD file BUE2C630.GSD
Bitmap files BUE2C630.BMP
PNO-ID C630 Hex
Baudrate max. 12 Mbaud
(is set automatically by the positioner)
Sync and Freeze modes are not supported
Diagnosis telegram No device-specific diagnosis
Parameter telegram No user parameters
The process data is configured in the positioner and in the PROFIBUS master.
Maximum 10 process values (total INPUT and OUTPUT) can be transferred.