121
Type 8692, 8693
english
Start-up, operation
process controller Type 8693
4.6 CAL.USER
Calibrating the actual value display and the inputs for the process values
The following points can be manually calibrated with this function:
Position display (• POS) 0 – 100%
Process set-point value display (S• P)***
Process actual value display (• PV)
EXIT
calibr. POS
CAL. USER
ENTER
ENTER
OPN
CLS
POS lower 0
EXIT
POS lower 0
INPUT
OK
*
OPN
CLS
POS upper 0
POS upper 0
INPUT
OK
*
calibr. PV
ENTER
EXIT
copyFACT->USER
RUN
Pressfor approx.
3 seconds
Reset the settings of CAL.USER
to factory settings
calibr. SP***
ENTER
SP 4mA 0
EXIT
SP 4mA 0**
INPUT
OK
*
SP 20mA 0
SP 20mA 0**
INPUT
OK
*
Calibration of signal type 4 – 20 mA
Calibration of circuit with PT 100
OK
*
Fig. 29: Operating structure CAL.USER-8693
Remove the CAL.USER auxiliary function to re-activate the factory calibration.
* If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.
** The signal type is displayed which is selected in the INPUT menu (4 – 20 mA; 0 – 20 mA; 0 – 5 V; 0 – 10 V).
*** Only if external set-point value default is set in the P.CONTROL / SETUP / SP-INPUT