EasyManua.ls Logo

Burkert 8693 - CAL.USER Calibrating the actual value display and the inputs for the process values

Burkert 8693
195 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120
Type 8692, 8693
english
Start-up, operation
process controller Type 8693
Alarm output for excessively large control deviation of the position controller: OUT DEV.X
Press the arrow keys to mark the
OUT DEV.X menu option and confirm with the selection key on the right
(SELEC).
Press the arrow keys to input the limit value for the permitted control deviation in the Lim. DEV.X 1.0% menu option and
accept with the selection key on the right (OK).
The permitted control deviation Lim. DEV.X XX must not be less than the dead band.
In the
OUT BIN type menu option input the required switching status (normally opened / normally closed)*.
Output of the current position with respect to a specified limit position: OUT POS
Press the arrow keys to mark the
OUT POS menu option and confirm with the selection key on the right (SELEC).
Press the arrow keys to input the the value of the limit position in the Lim. POS 0% menu option and accept with the
selection key on the right (OK).
In the
OUT BIN type menu option input the required switching status (normally opened / normally closed).
OUT BIN1 normally opened normally closed
POS > LIM
0 V
24 V
POS < LIM
24 V 0 V
Output of message: Actuator in safety position: OUT Safepos
Press the arrow keys to mark the
OUT Safepos menu option and confirm with the selection key on the right
(SELEC).
In the OUT BIN type menu option input the required switching status (normally opened / normally closed).
Output sensor break: OUT ERR SP/CMD*
Press the arrow keys to mark the
OUT ERR SP/CMD menu option and confirm with the selection key on the right
(SELEC).
In the
OUT BIN type menu option input the required switching status (normally opened / normally closed).
Output sensor break: OUT ERR PV*
Press the arrow keys to mark the
OUT ERR PV menu option and confirm with the selection key on the right
(SELEC).
In the OUT BIN type menu option input the required switching status (normally opened / normally closed).
Output operating state AUTOMATIC / MANUAL: OUT remote
Press the arrow keys to mark the
OUT remote menu option and confirm with the selection key on the right
(SELEC).
In the OUT BIN type menu option input the required switching status (normally opened / normally closed).
OUT BIN1 normally opened normally closed
AUTOMATIC operating state 0 V
24 V
MANUAL operating state 24 V 0 V
Normally closed output, in switched state low (0 V)
Normally opened output, in switched state high (24 V)
* only possible if signal level fault detection activated (see chapter entitled "SIG-ERROR")

Table of Contents

Other manuals for Burkert 8693

Related product manuals