Extended C-Code Settings for Special Cases
This section lists recommended parameter settings for specific types of batteries, where
the recommended settings are different from the default settings.
Intrinsically Safe Batteries
Before servicing intrinsically safe (I/S) batteries, set the following C-Code parameters as
specified:
Parameter Setting
Charge
0.10 C*
Discharge
0.10 C*
Charge Method
DC charge
End of Discharge
0.96V/cell
Hawker SLA Batteries
Before servicing Hawker SLA batteries, set the following C-Code parameters as specified
below (any parameters not listed here should be left at their default settings):
Parameter Setting
Discharge
0.40 C
Max. Standby Voltage
2.35V/cell
Max. Charge Voltage
2.60V/cell
End of Discharge
1.62V/cell
Gell SLA Batteries
Use the SLA default settings for Gell batteries.
* Recommended settings. You can try setting the charge and discharge rates to higher values to speed up servicing;
however, if fault codes appear, you must lower the rates.