5.3.3 Installing the steam distributors
Detailedinformationontheinstallationofsteamdistributionpipes41-..,61-.../81-...andOptiSorp
steamdistributionsystemcanbefoundintheseparate“MountingInstructions”forthisproducts.
Guidelines for dimensioning the ventilation ducts
– Tofacilitatetheinstallationofthesteamdistributionpipesandforcontrolpurposes,asufciently
sized control opening should be planned.
– Withintherangeofthehumidicationdistance,theventilationductshouldbewaterproofed.
– Airductspassingthroughcoldroomsshouldbeinsulatedtopreventthehumidiedairfromcon-
densing along the duct wall.
– Poorairowconditionswithintheairduct(e.g.causedbyobstacles,tightbends,etc.)canlead
tocondensationofthehumidiedair.
Steam distribution pipes must not be mounted to round ducts.
Ifyouhavequestionsrelatingtothedimensioningofventilationductsincombinationwithsteam
humidiersCondairCP3,contactyourCondairsupplier.