34
5.3.4 Positioning and mounting of the fan unit
FAN3SCP...M
FAN3SCP...MFC
FAN3SCP...L
m
D
max. 8kg/h 15kg/h 30kg/h 45kg/h
A min. 4.0 m 6.0 m 8.0 m 10.0 m
B min. 1.0 m 1.0 m 1.0 m 1.5 m
C min. 2.2 m 2.2 m 2.2 m 2.2 m
D min. 1.0 m 1.0 m 1.0 m 1.5 m
E min. 0.15 m
E max.
(max.steamhoselength) 4.0 m (recommended: 2.0 m)
Note:Theminimumspacesinthetableapplyforaroomatmosphereof15°Candmax.60%rh.For
lowertemperaturesand/orhigherhumiditythevaluesshouldbeadjustedaccordingly
Note:Inordertoachieveauniformdistributionofthehumiditywithintheroom,additionalfactors
suchastheroomsize,theroomheight,etc.,mustbetakenintoconsiderationbesidesobservingthe
minimumdistances.Ifyouhavequestionsconcerningthedirectroomhumidication,pleasecontact
your Condair supplier.
Furtherinformationisprovidedintheseparateinstallationandoperatinginstructionsforthefanunit.
Thefanunitismountedonthewallseparately above the unit.Toallowthesteamcomingfrom
thefanunittospreadoutevenly,withoutcondensingonobstacles(ceilings,joists,pillars,etc.),the
followingminimumdimensionsmustbeobservedwhenselectingthelocationforthefanunit.