STARTUP:
CP3 PRO
INIT MODULe
XXXXXXXXXXXXXXXXXXXX
Menu Set
Thesteamhumidiercarriesoutasystem test, during which all the
LEDslightupandtheoppositedisplayisshown.
Ifafailureoccursonthesystemtest,acorrespondingerrormessage
is shown in the display.
After the system test the unit is in normal operation mode. The
display shows the standard operating display (rst page of the
indicationlevel).
Note:Thecontentsofthestandardoperatingdisplaydependsonthe
actualoperatingstatusandonthecongurationoftheCondairCP3
andcandifferfromtheoppositedisplay.
As soon as the humidity controller or the humidistat requires humidity,
powerisswitchedonforheating.Theinletvalveopens(slightdelay)
andthesteamcylinderllswithwater.Assoonasthesubmerged
electrodesheatthewaterupthegreenLEDlightsupandafterafew
minutes(approx.5–10minutes,dependingontheconductivityofthe
water)steamisproduced.
Standby
CP3 P45 400V3
XXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXX
2014-01-21 12:00:00
Menu Set
Demand :100%
CP3 P45 400V3
XXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXX
2014-01-21 12:00:00
Menu Set
Note:IftheCondairCP3isoperatedwithwateroflowconductivityitmayhappenthatthemaximum
steamcapacityisnotreachedintherstfewhoursofoperation.Thisisnormal.Assoonasthe
conductivityhasreachedasufcientlevel(duetothevaporisationprocess)thehumidierwillreach
the maximum steam capacity.
6. Actuate the unit switchofthesteamhumidier.Switch lights up.
6.3 Notes on operation
6.3.1 Remote operating and fault indication
Viatheoperatingandfaultindicationthefollowingoperatingstatusareshownremotely:
Activated remote
indication relay
When? Display on unit
H1 “Error” Amalfunctionispresent,furtheropera-
tion is not possible, the heating voltage is
interrupted
RedLEDlights
An error message is shown in the
display
H2 “Service” Steam cylinder maintenance is due. The
unitremainsoperationalforacertaintime
YellowLEDlights
The service warning message is
shown in the display
H3 “Steam demand”
Steamdemand/
Steam production
GreenLEDlights
The standard operating display is
shown.
H4 “Unit on”
Unitreadyforoperation Unitswitchlights
The standard operating display is
shown.
6.3.2 Notesontheoperationatambienttemperatures≤0°C
Ifduringoperationambienttemperatures≤0°Cmustbeexpected(operationoftheCondairCP3
inaprotectivehousingoutsidethebuilding),thestandbydrainingfunctionmustbesetto“Full”and
theperiodoftimeinstandbyoperationafterwhichanautomaticcylinderdrainingtakesplacemust
besetto1hour(seechapter6.7.9).