6.7.7 Activating/Deactivating fault current relay operation
Settings
On/O Timer :Set
GFCI-Mode :On
Multi-Mode :Sequence
Power Limit :Set
Water Manag.:Set
Esc Set
Select “GFCI-Mode”inthesettingsmenu,thenpressthe<Set>key.
IntheupcomingmodicationdialogueselectwhetherornottheCondair
CP3isconnectedtoafaultcurrentrelayprotectedmainssupply.
Factorysetting: On
Options: On (mainssupplywithfaultcurrentrelayprotec-
tion)
Off (mainssupplywithoutfaultcurrentrelay
protection)
On/O Timer
Event 1 :06:00
Event 2 :22:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc Set
Event 2
Time :22:00
Mode :On
Weekday :Mo-Fr
Esc Set
6.7.8 Setting the operation mode for multiple units
Settings
GFCI-Mode :On
Multi-Mode :Sequence
Water Manag.:Set
On/O Timer :Set
Remote Test :Set
Esc Set
Select “Multi-Mode” in the settings menu, then press the <Set> key.
Intheupcomingmodicationdialogueyoudeterminehowthedemanded
steam capacity is shared among the units.
Factorysetting: Sequence
Options: Sequence(sequentialloadsharing)
Parallel (evenloadsharing)
Note:ThissettingisavailableonlyonmainmoduleAofmultipleunits.
– On/Offtimeractivated:
Ifthetimerisactivated,uptoeightswitch-
ingpoints(events1-8)withdifferentOn/
Offeventscanbedened.
Eachswitchingpointisdenedbyaweek-
dayorweekdayrange,theswitchingpoint
and the operating mode.
Congurationnotes:
– thesettingsofaneventremainactiveuptothenextevent.
– the software does not check the plausibility of the timer settings.
Therefore,makesureyoursettingsmakesense.
– theOn/Offtimeroverridesallothertimers.
Notes on Multi-Mode settings
– Sequence:thedemandisdistributedasfollows:therstcylinder(ModuleA)takes0–50%of
thedemandandthesecondcylinder(ModuleB)51–100%.Inordertoensurebalancedcylinder
operatinghourstheparameters“Seq.Rotation”and“Seq.Interval”mustbesetaccordinglyinthe
engineering level.
– Parallel:Thedemandisdistributedevenlyonbothcylinders,i.e.withademandof50%both
cylindersworkingwith50%demand.