6.6 Interrogation functions
6.6.1 Interrogation of the operating information in the indication level
In the normal operating mode the operating and display unit is in the indication level. The indication
levelformsaloopthatincludesseveralpagesholdingoperatinginformationwhichcanbeaccessed
withthearrowkeys.Thevariousdisplaysoftheindicationlevelareshownbelow.
Standard operating display
Theappearanceofthestandardoperatingdisplaydependsontheactualoperatingstatusandthe
congurationoftheCondairCP3.Thefollowingdisplayarepossible.
Demand :100%
CP3 P90 400V3
Limiter : 70%
2014-01-21 12:00:00
Menu Set
Standard operating display with control via the external controller
– Standby(nohumiditydemand)orDemand%(humiditydemand
present)
– Setsupplyairlimitationin%*
*thisparameterappearsonlyifexternalsupplyairlimitationisacti-
vated
Act.Humidity: 75%rH
CP3 P90 400V3
Hum.Setpoint: 50%rH
Lim.Humidity: 60%rH
Lim.Range : 70-90%
Menu Set
Standard operating display with control via the internal controller
– Actualhumidityin%rh
– Setnominalhumidity%rh
– Setsupplyairlimitationin%**
– Setrangeforsupplyairlimitationin%**
** these parameters appear only if internal supply air limitation is
activated
Info page: Settings
Software :1.14LA02
CP3 P90 400V3
Controlsign.:0-10V
Limitsignal :0-10V
Modbus Addr.:1
Menu Set
– Softwareversion(1.14)/languageversion(LA02)
– Setcontrolsignalrange(signalY)
– Setcontrolsignalrangeforthesupplyairlimitation(signalZ).Ap-
pearsonlyifsupplyairlimitationisactivated.
– SetModbusaddressoftheunit
Info page: Performance data
Power Limit :100%
CP3 P90 400V3
Request A :50%
Request B :50%
∑ Steam :45kg/h
Menu Set
– Setpowerlimitationin%
– ActualhumiditydemandunitAin%rh
– ActualhumiditydemandunitBin%rh(ifpresent)
– Actualsteamcapacityoftheunitinkg/h
Info page: Steam cylinder type and operating hours
Cylindertype:A644
CP3 P90 400V3
Operating Hours
Cylinder A :20h
Cylinder B :20h
Menu Set
Steam cylinder type
– OperatinghoursofthesteamcylinderAsincethelastreset.
– OperatinghoursofthesteamcylinderBsincethelastreset.
Info page: Drain settings
Drain Factor:1.0
CP3 P90 400V3
Conductivity:>125µS
StandbyDrain:Full
Forced Drain:O
Menu Set
– Setdrainfactor
– Conductivityofthewater
Set draining type in standby operation
– Settimeintervalforforceddraining