6.7.9 Water management settings
Select “Water Manag.”inthesettingsmenu,thenpressthe<Set>key.
The water management settings menu appears.
Pressthe< > and < >keysinordertoselecttheindividualsettingsand
press the <Set>keytocallupthemodicationdialoguefortheselected
setting.
Settings
Multi-Mode :Sequence
Water Manag.:Set
Remote Test :Set
GFCI-Mode :On
Date :19.10.07
Esc Set
Description of the water management settings
Conductivity: Selectingtheconductivityrangeofthesupplywater.
Factorysetting: >125μS/cm
Options: >125μS/cm, <125μS/cm
Drain Factor: Settingthedrainfactor
Factorysetting: 1.0
Settingrange: 0.5...2.0
StandbyDrain: Selectingthetypeofdrainingwhichtakesplaceafteracertaintime(see
followingsetting)ofstandby operation.
Factorysetting: Full
Options: Full (completedraining)*
Partial(partialdraining)**
Off(drainingdeactivated)
* with outdoor operation it is mandatory to use this setting.
** Thecylinderisdrainedsofarthatthewaterdoesnottouchtheelec-
trodes any longer.
StandbyDelay: Settingtheperiodoftimeinstandbyoperationafterwhichanautomatic
cylinderdrainingtakesplace.
Factorysetting: 72 hours
Settingrange: 1...720 hours ***
***withoutdooroperationitismandatorytosettheperiodoftimeinstandby
operation after which an automatic cylinder draining takes place to
1 hour.
Force Drain: Activating/Deactivatingtheforceddrainingwhichtakesplaceafteracer-
taintimeofoperation.Theforceddrainingtakesplacealsoduringsteam
production.
Factorysetting: Off
Options: On (Forceddrainingactivated)
Off(Forceddrainingdeactivated)
Force Delay: Settingthetimeofoperationafterwhichaforceddrainingtakesplace.
Factorysetting: 72 hours
Settingrange: 1...720 hours
Force Delay :72h
Water Manag.
Drain Factor:1.0
StandbyDrain:Full
StandbyDelay:72h
Conductivity:>125µS
Force Drain :On
Esc Set