Water supply
Thewatersupplyistobecarriedoutaccordingtothegurefoundinchapter5.4.1andtheapplicable
localregulationsforwaterinstallations.Theindicatedconnectionspecicationsmustbeobserved.
– Theinstallationoftheltervalve(accessory“Z261”,alternativelyashut-offvalveanda5µm
waterltercanbeused)shouldbemadeascloseaspossibletothesteamhumidier.
– Admissible mains pressure 1.0 to 10.0 bar (hammer-free system)
Formainspressures>10bar,theconnectionmustbemadeviaapressurereducingvalve(ad-
justedto1.0bar).Formainspressures<1.0barpleasecontactyourCondairsupplier.
– Notesonwaterquality:
– ForthewatersupplyoftheCondairCP3,useexclusivelyuntreated drinking water.
– Theuseofadditivessuchascorrosioninhibitors,disinfectants,etc.is not allowed, since
theseadditivesmayendangerhealthandaffectproperoperation.
– IftheCondairCP3shallbeoperatedwithsoftenedorpartlysoftenedwater,pleasecontact
your Condair supplier.
– The connection material must be pressure-proof and certiedforuseindrinkingwatersystems.
– Important!Beforeconnectingthewaterline,thelineshouldbewellushedout.
CAUTION!
Thethreadatthehumidierconnectionismadeofplastic.Toavoidovertightening,theunion
nutofthewaterpipemustbetightened by hand only.
Water drain
Thewaterdrainistobecarriedoutaccordingtothegurefoundinchapter5.4.1andtheapplicable
localregulationsforwaterinstallations.Theindicatedconnectionspecicationsmustbeobserved.
– Makesurethatthedrainpipeiscorrectlyxedandeasilyaccessibleforinspectionsandcleaning
purposes.
– Thedrainingtemperatureis:80…90 °C (approx.70...80°Cwithactivateddrainwatercooling).
Usetemperature-resistantinstallationmaterialsonly!
5.4.2 Notes on water installation