55
Settings
Cylinder :Set
Power Limit :Set
On/O Timer :Set
Controls :Set
GFCI-Mode :On
Esc Set
6.7.5 Setting the capacity limitation
Select “Power Limit”inthesettingsmenu,thenpressthe<Set>key.
Withtheparametersinthe“PowerLimit”submenuyoudeterminewhether
theCondairCP3istobeoperatedwithaxcapacitylimit(factorysetting)
or whether it is to be operated with a timer controlled capacity limitation.
Note:setthedesiredcapacitylimitationin % of the maximum capacity
ofthehumidier.
– Operation with xcapacitylimit:
Timer deactivated, capacity limit adjust-
able(factorysetting:100%,Settingrange:
30...100%).
– Timer controlled capacity limitation:
Ifthetimerisactivated,uptoeightswitching
points(events1-8)withdifferentcapacity
limitscanbedened.
Eachswitchingpointisdenedbyaweek-
dayorweekdayrange,theswitchingpoint
and the capacity limit.
Congurationnotes:
– thesettingsofaneventremainactiveuptothenextevent.
– the software does not check the plausibility of the timer settings.
Therefore,makesureyoursettingsmakesense.
– theOn/Offtimer(seechapter6.7.6)overridesthecapacitylimittimer.
Power Limit
Power Limit :100%
Timer :O
Esc Set
Power Limit
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc Set
Event 2
Time :18:00
Power Limit :50%
Weekday :Mo-Fr
Esc Set
Settings
Power Limit :Set
On/O Timer :Set
GFCI-Mode :On
Cylinder :Set
Multi-Mode :Sequence
Esc Set
6.7.6 ConguringtheOn/Offtimer
Select “On/Off Timer”inthesettingsmenu,thenpressthe<Set>key.
Withtheparametersinthe“On/OffTimer”submenuyoudeterminewhether
ornottheCondairCP3istobeswitchedonandofftimercontrolled.
– On/Offtimerdeactivated:
On/O Timer
Timer :O
Esc Set