50
6.6.2 Interrogation of unit information
Selectthelistwiththeunitinformation:
Path:Main menu > Info > Unit Status
Press< > and < >keys,inordertoselecttheunitinformationavailable
inthelist:
1 Total operating hours since the initial commissioning.
2 ActualcurrentunitA(andB)
3 Actualstatusoftheremoteindicationrelay“Steam”
4 Actualstatusoftheremoteindicationrelay“Service”
5 Actualstatusoftheremoteindicationrelay“Error”
6 Actualstatusoftheremoteindicationrelay“Uniton”
7 Actual signal value at analog output 1 (corresponds to the actual
steamcapacityconvertedtothesignalrangeof0...10V)
8 Actualsignalvalueatanalogoutput2(0...10V)
9 CalculatedmeandraintimeinsecondsofunitA(andB)
10 CurrentaveragerequestofunitA(andB)
11 ActualstatusofthemaximumlevelsensorinthesteamcylinderA
(andB)
12 Countershowingthenumberoftimesthemaximumlevelinthesteam
cylinderA(andB)hasbeenexceeded
13 ActualstatusoftheinletvalveofunitA(andB)
14 ActualstatusofthedrainpumpofunitA(andB)
15 ActualstatusofthemaincontactorofunitA(andB)
Pressthe<Esc>keyseveraltimestoquittheunitinformationlistandto
return to the standard operating display.
Info Page: Timer settings
Timer
CP3 P90 400V3
On/O Timer :O
Power Limit :O
Hum.Setpoint:Off
Menu Set
– ActualstatusofOn/Offtimer
– Actualstatusofpowerlimittimer
– Actualstatusofhumiditysetpointtimer(appearsonlyifinternalP/PI
controllerisactivated)
Remote Service
O
Remote Error
O
Remote Unit On
On
Remote Analog Out-1
0.0 V
Remote Analog Out-2
0.0 V
Average Drain Time
A 0.0 s B 0.0 s
Max. Level Sensor
A O B O
Max. Level Counter
A 0 B 0
Inlet Valve
A O B O
Outlet Pump
A O B O
Main Contactor
A O B O
Average Request
A 100% B 0 %
Unit Status
0h
Actual current
A 0.0 A B 0.0 A
System Operating Hour
2014-01-21 12:00:00
Esc Set
1
2
4
5
6
7
8
9
10
11
12
13
14
15
Remote Steam
O 12.00.00
3