EasyManua.ls Logo

Condair CP3 - 5.5.3 Wiring diagram Option CVI and Option Trafo; 5.5.4 Fuses F5 for heating voltage supply

Condair CP3
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
5.5.4 Fuses F5 for heating voltage supply
Heating voltage Max. steam
capacity
[kg/h]
Model Condair CP3 Unit
design
**
Nominal
power
[kW]
Nominal
current
[A]
Main
fuses F5
[A]
Basic... Pro...
400V3
(400V/3~/50...60Hz)
5...8 5...8 5...8 EK 6.0 8.7
3x10
9...12 9...12 9...12 EK 9.0 13.0 3x 16
13...15 13...15 13...15 EK 11.3 16.3
3x20
16...20 16...20 16...20 EG 15.0 21.7 3x 25
21...25 21...25 21...25 EG 18.8 27.1 3x 35
26...30 26...30 26...30 EG 22.5 32.5
3x40
31...42 31...42 31...42 EG 31.5 45.5 3x50
43...45 43...45 43...45 EG 33.8 48.8 3x 63
52 52 52 DG
2x19.5 2x 28.1 2x(3x40)
60 60 60 DG 2x 22.5 2x 32.5 2x(3x40)
70 70 70 DG 2x 26.3 2x37.9 2x(3x50)
80 80 80 DG 2x30.0 2x 43.3 2x(3x50)
90 90 90 DG 2x 33.8 2x 48.8 2x(3x63)
105 -- 105 DG+EG 3x 26.3 3x37.9 3x(3x50)
120 -- 120 DG+EG 3x30.0 3x 43.3 3x(3x50)
135 -- 135 DG+EG 3x 33.8 3x 48.8 3x(3x63)
152 -- 152 2xDG 4x 28.5 4x 41.1 4x(3x50)
160 -- 160 2xDG 4x30.0 4x 43.3 4x(3x50)
180 -- 180 2xDG 4x 33.8 4x 48.8 4x(3x63)
230V3
(230V/3~/50...60Hz)
5...8 5...8 5...8 EK 6.0 15.8
3x20
9...15 9...15 9...15 EK 11.3 29.6 3x40
16...21 16...21 16...21 EG 15.8 41.4 3x50
22...26 22...26 22...26 EG 19.5 51.2 3x 63
27...30 27...30 27...30 EG 22.5 59.1
3x80
44 44 44 DG 2x 16.5 2x 43.4 2x(3x63)
50 50 50 DG 2x 18.8 2x49.3 2x(3x63)
60 60 60 DG 2x 22.5 2x59.1 2x(3x80)
75 -- 75 DG+EG 3x 18.8 3x49.3 3x(3x63)
90 -- 90 DG+EG 3x 22.5 3x59.1 3x(3x80)
100 -- 100 2xDG 4x 22.5 4x59.1 4x(3x63)
120 -- 120 2xDG 4x 22.5 4x59.1 4x(3x80)
230V1
(230V/1~/50...60Hz)
5 5 5 EK 3.8 16.3 20
6...8 6...8 6...8 EK 6.0 26.1 35
** EK=Singleunitsmall/EG=Singleunitlarge/DG=Doubleunitlarge
Note:Theminimumcrosssectionofthesupplycablemustcomplywiththelocalregulations.
5.5.3 Wiring diagram Option CVI and Option Trafo
Option CVI Option Trafo
M
L1 N
Q5
K1
XE1
F5
L1 L2 L3
L1 L2 L3
400 V/3~/50..60 Hz
230 V/3~/50..60 Hz
N PE
L1 L1 L2 L3 N PE
F7
6.3 AT
B3
K
B2
B1
∆p
max.
B3
K
B2
B1
∆p
max.
M
L1 N
0 500 480 440 400 0
Si
220
460
PE
L1 L1 L2 L3L3 PE
F7
F8
K1
L1 L2 L3
Q5
F5
L1 L2 L3
400 V/3~/50..60 Hz
PE
XE1
F7/F8 = 6.3 AT
Trafo
PEPESC2SC1NL1
X1
MAIN SUPPLY
PEPESC2SC1NL1
X1
MAIN SUPPLY

Table of Contents

Related product manuals