53
– Hum.Control: Selectingthecontroltype.
Factorysetting: Extern
Options: Extern(externalcontinuouscontroller),
24VOn/Off(externalOn/Offhumidistat),
Int. (P)(InternalPcontroller)
Int. (PI)(InternalPIcontroller)
– Controlsign.: Selectingthecontrolsignal.
Note:ThissettingisavailableonlyiftheinternalorexternalPorPIcontrol-
ler is activated.
Factorysetting: 0–10V
Options: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V,
0–20mA, 4–20mA
– Hum.Setpoint: ThismenuitemisavailableonlyiftheinternalPorPIcontrollerisactivated.
Withtheparametersinthe“Hum.Setpoint”submenuyoudeterminewhether
theCondairCP3istobecontrolledwithaxhumiditysetpoint(factoryset-
ting)orwhetheritistobeoperatedtimercontrolledwithdifferenthumidity
setpoints.
– Control with xhumiditysetpoint:
Timerdeactivated,humiditysetpointadjust-
able(factorysetting:50%rH,Settingrange:
15...95%rH)
– Timer controlled with different humidity setpoints:
Ifthetimerisactivated,uptoeightswitching
points(events1-8)withdifferenthumidity
setpointscanbedened.
Eachswitchingpointisdenedbyaweekday
orweekdayrange,theswitchingpointand
the humidity setpoint.
Congurationnotes:
– thesettingsofaneventremainactiveuptothenextevent.
– thesoftwaredoesnotchecktheplausibilityofthetimersettings.
Therefore,makesureyoursettingsmakesense.
– theOn/Offtimer(seechapter6.7.6)overridesthehumiditysetpoint
timer.
– P-Band: Settingtheproportionalrangein%fortheinternalP/PIcontroller.
Note:ThissettingisavailableonlyiftheinternalPorPIcontrollerisactivated.
Factorysetting: 18 %
Settingrange: 6...65 %
– Integr.-Time: SettingtheintegraltimeinminutesfortheinternalPIcontroller.
Note:ThissettingisavailableonlyiftheinternalPIcontrollerisactivated.
Factorysetting: 8 minutes
Settingrange: 1...60 minutes
Hum.Setpoint
Hum.Setpoint:50%rH
Timer :O
Esc Set
Hum.Setpoint
Event 1 :06:00
Event 2 :18:00
Event 3 :--:--
Timer :On
Event 4 :--:--
Esc Set
Event 2
Time :18:00
Hum.Setpoint:30%rH
Weekday :Mo-Fr
Esc Set