INSTALLATION
22
SAFERY LASER SCANNER
DISTANCE TO WALL
NOTE
The Safety Zone must maintain a tolerance of at least 40 mm from
any wall or fixed object (a and b in the image above).
This value is
generally enough to guarantee normal operation, however accord-
ing to the real reflectance characteristics of the wall, a higher value
may be necessary. The Teach In feature in DLSentinel automatically
applies a tolerance of 100 mm. This can be changed manually if nec-
essary. Verify the correct placement of the Safety Zone during the
initial configuration before commissioning.