EasyManuals Logo

Delta Electronics AC Motor Drive VFD-VE Series User Manual

Delta Electronics AC Motor Drive VFD-VE Series
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
Chapter 4 Parameters|
4-94 Revision August 2008, 03VE, SW V2.04
 Pr.05-26 to Pr.05-28 are used to set allowable slip level/time and over slip treatment when the
drive is running.
05-29  Hunting Gain Unit: 1
Control
mode
VF VFPG SVC
Factory setting: 2000
Settings 0 to 10000 (0: disable)
 The motor will have current wave motion in some specific area. It can improve this situation by
setting this parameter. (When it is high frequency or run with PG, Pr.05-29 can be set to 0.
when the current wave motion happens in the low frequency, please increase Pr.05-29.)
05-31 Accumulative Motor Operation Time (Min.) Unit: 1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 00
Settings 00 to1439
05-32 Accumulative Motor Operation Time (Day) Unit: 1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 00
Settings 00 to 65535
 Pr. 05-31 and Pr.05-32 are used to record the motor operation time. They can be cleared by
setting to 00 and time won’t be recorded when it is less than 60 seconds.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics AC Motor Drive VFD-VE Series and is the answer not in the manual?

Delta Electronics AC Motor Drive VFD-VE Series Specifications

General IconGeneral
BrandDelta Electronics
ModelAC Motor Drive VFD-VE Series
CategoryController
LanguageEnglish

Related product manuals