Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04 4-77
02-11~14=3
02-11~14=4
Fcmd=60Hz
02-19=10Hz
02-20=2Hz
02-21=40Hz
02-22=2Hz
H
38Hz
40Hz
42Hz
10Hz
12Hz
8Hz
T
02-31 Brake Delay Time Unit:0.001
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 0.000
Settings 0.000~65.000 Sec
When the AC motor drive runs after Pr.02-31 delay time, the corresponding multi-function
output terminal (12: mechanical brake release) will be ON. This function should be used with
DC brake.
Moto r sp ee d/
Output frequenc y
DC br ake
DC br ake
07 -0 2
DC br ake
time during
star t-up
07 -0
3
DC br ake
time during
stop pi ng
Mul ti- f unc ti on o utpu t
(me cha ni cal b rake re le ase )
Pr. 02 -11 to 0 2-1 4=12
Mec han i cal br ake
02 -3 1 b rake d el ay ti me
bounce time of mechanical brake
RUN/STOP
ON STOP
br ake d
release
br ake d
02-32 Output Current Level Setting for External Terminals Unit:1
Control
mode
VF VFPG SVC FOCPG TQRPG
Factory setting: 0